X-CELLMK2 COMBI-: SINEWAVE INVERTER \ BATTERY CHARGER SPECIFICATION


 

SPECIFICATION

MODEL:- 1500SL-12, [1500SL-24], 3000SL-12, [3000SL-24].

Inverter Section

Nominal battery voltage per model 12V [ 24V ]
Input voltage range per model 9.5-16V [ 19-32V ]
Output voltage 200~240Vac.
Output frequency 50 Hz.
Total Harmonic Distortion output THD < 2%.
Dynamic behaviour 0 - 100% 0.5 ms
Asymmetrical load max. Up to nominal output power
Overload and short circuit protection Automatic disconnection with 5 time restart attempt
Overheating temperature protection Acoustic warning before shut-off. Automatic restart
Power factor range 0.1-1
Power saving function (disable / enable)
Maximum efficiency 85-90%

Nominal power (W) 1500W Models.

Maximum power 30 min (W) 1700W.
Maximum power 3 min (W) 2300W.
Maximum power 5 sec (W) 3000W.
Maximum load Up to short circuit.

Nominal power (W) 3000W Models.

Maximum power 30 min (W) 3500W
Maximum power 3 min (W) 4500W
Maximum power 5 sec (W) 6000W
Maximum load Up to short circuit

Battery Charger Section

Maximum input voltage 265 Vac, 350 V peak
Minimum input voltage Adjustable 150-230Vac
Input Frequency range 45~63Hz
Adjustable charging current:-
1500w versions:- * 0-50A [ 0-35A ]
3000w versions:- * 0 - 100A:- [ 0-70A]
*Setting of AC INPUT current POWER SHARING 0 to 15A

Solar Charge regulator

Solar Charge Regulator-Floating.
Maximum Open Circuit Voltage 25V [ 45V ].
Maximum charging current 30A

Battery Charge Monitoring

*Low battery disconnection voltage 10.8V [ 21.6V ]
*Low voltage 10.8V~12.0V (11.6V) [ 21.6V~24.0V (23.2V) ].
*End of charge cycle voltage 14.2V~15.0V (14.4V) [ 28.4V~30.0V (28.8V) ].
*Equalization voltage every 25 cycles 15.1V~15.5V (15.3V) [ 30.2V~31.8V (30.6V) ].
*Floating voltage 13.3V~13.7V (13.5V) [ 26.6V~27.4V (27.0V) ].
*Absorption charge time 0~4h (2h)
Temperature compensation (Optional) -3mV / C / cell

General data.

AC By pass time (UPS-Mode) 20 ms max.
Potential free Multifunction contact 5Amps -250Vac / 7 Amps - 60V dc x 2.
Max Current at Transfer relay 15 Amps / AC 220V 30Amps / AC220V.
Operating temperature -20C to +55C.
Fan forced ventilation internal sensor From 45C - over 75C will cause trip out.
Protection index IP IP20.
Net Weight1500W Models 20.00kg, 3000W Models 28.0kg.
Dimension L*W*H (mm) 1500W Models:- 350 x 285 x 185, 3000W Models:- 510 x 285 x 185.

Note

Factory settings shown ( ), 24V models shown [ ], user adjustable shown *.

MODE OF OPERATION

The low dc voltage is converted into a pure sine wave using solid state power electronic devices, the frequency of the output voltage is crystal controlled for accuracy and stability. The dc input voltage is sampled in order to detect either a low or a high input and generates an alarm signal plus an output drive shutdown. Similarly the internal heat sink temperature is monitored and if a high temperature is detected an alarm signal plus an output drive shutdown occurs until the temperature has dropped to a safe level when the unit will automatically switch back on. The dc input current draw is measured in order to detect an overload, if an overload exists an alarm plus an output drive shutdown is generated. If during the slow start switch on an overload is generated the unit will continue to generate the alarm/shut down signal until the overload is reduced.

Click here for Contact Information