X-CELLMK2 COMBI SINEWAVE INVERTER/BATTERY
CHARGER INSTALLATION INSTRUCTIONS


INSTALLATION INSTRUCTIONS
Important Notes:-
When installing the inverter fit a suitable Residual Current Circuit
Breaker and one or more suitably rated Mains Circuit Breakers between the
output of the inverter and any mains loop. This recommendation is for safety
reasons, 230 volts can be dangerous if equipment is not installed and protected
correctly.
There is a considerably greater voltage drop on cable runs of low voltage,
high current systems than high voltage, low current systems. This simple
formula can be used to calculate the expected voltage drop :-
E (volts drop) = 0.0164 x I (current flow) x L (length in metres
including positive and negative leads)/ S (cable size in mm)
For maximum efficiency and safety it is important to reduce the distance
from battery to inverter to the practical minimum. The cable length of
the AC supply from inverter to appliance is relatively unimportant.
Connecting to the Battery Bank.
Note Caution
Connecting a battery bank with the wrong battery voltage to the Combi
will cause irreparable damage. Ensure that the Combi DC voltage rating
matches the battery bank voltage to which it is to be connected.
Prepare the batteries
for connection.
Prepare battery
cables, if necessary press on cable tabs/shoes.
Connect the red
cable to the Battery Positive (+).
fuse/circuit
breaker and the black cable to battery Minus (-).
Take care when
connecting the second cable to the battery, as a spark is produced, this
is caused for a short time due to high current flowing in the Combi input
circuit to charge the capacitors.
This is another
reason to install a battery fuse/circuit breaker. For this reason follow
strictly the safety measures described in the comprehensive manual supplied
with the Combi.
DO NOT INSERT THE BATTERY FUSE AT THIS STAGE.
Connection to the AC OUTPUT.
The AC output must
be connected to the screw terminal AC OUTPUT. For this use a 3 core cable
with a conductor cross section of 2.5 mm². Connections are marked
as follows "OUT / N" = Neutral, "GND" = Earth, "OUT / L" = Live or Active.
Caution: High
voltage can be at the AC output, ensure the Combi is not connected or switched
on when making AC connections.
Connection to the AC INPUT
The AC input supply
from the mains supply or from a generator must be connected to the screw
terminals AC INPUT. For this use a 3 core cable with a conductor cross
section of 2.5 mm². Connections are marked as follows "IN / N" = Neutral,
"GND" = Earth, "IN / L"= Live or Active.
Connect the Solar module: SOLAR IN +/-
Only Solar modules
with an output conforming to the specification should be connected to these
terminals. Under no circumstances should any other energy source i.e. wind
generator be connected to these terminals.
Depending on
the power of the modules the cable cross section should be 2.5 mm²
up to 6 mm². Before connecting it is necessary to check with a Voltmeter
that the voltage of the Module meets the following values:
Combi -1500SL
-12 / Combi - 3000SL -12 is 17-25V / 30A.
Combi -1500SL
-24 / Combi - 3000SL -24 is 34-45V / 30A.
Connection to Aux 1 & Aux 2:
On these three terminals
is a volt free change-over contact capable of switching a maximum current
and voltage of 16A/250V ac. The " multi-display " on the front of the Combi
can show the status of these contacts.
Click here for Contact
Information