BATTERY INSTALLATION INSTRUCTIONS


 

INSTALLATION

The Batteries should be installed in a dry and well ventilated location.
The Batteries should be installed in a manner so as to restrict their movement horizontally and vertically.
Install Batteries where there is protection against metallic objects coming into unintentional contact with the terminals.
Battery cables should not depend on spring tension for mechanical connection to them.
Use correct size cable for installation and fit an external battery isolation switch adequately rated.
If possible install the batteries in a cool environment to prolong their active life.
If charged from a wind generator or solar cell ensure the voltage controller is set to provide no more than 14.1 volts if left connected for any length of time.

nb. For further information on the safe installation of batteries on board boats see the Recreational Craft Directive IV Edition.

Recommended Cable Sizes

CABLE SIZE IN mm
RATING 100% DUTY CYCLE
RATING 60% DUTY CYCLE
RATING 30% DUTY CYCLE
16
135
175
245
25
180
230
320
35
225
290
410

The cable specified is high grade double insulated weld cable, as this cable has a high number of strands it remains flexible in use.
 

When using power at low voltage (12/24) to feed an inverter 99% of the losses will be at the low voltage therefore when selecting cable size always choose the largest size possible. To give you an idea of the voltage drop expected use the simple formula :-
E (volts drop) = 0.0164 x I (current flow) x L (length in metres including positive and negative leads)/ S (cable size in mm)