X-ACT INSTALLATION
![]()
|
|
|
|
|
|
Electrical Wiring
Amp Versions
Red 24/02 cable = Power Input and should be protected at source by
a Amp fuse.
Yellow 24/02 cable = Stabilized Power Output.
Black 24/02 cable = Electronics 0 volt supply.
12 volt 15 Amp & 25 Amp and 12 volt 50 Amp & 24 volt 25 Amp
Versions
The wiring for the input & output connections must be suitably
rated for rated current.
A suitable protection device should be fitted at source to match units
specification.
The 0 volt cable needs to be 16/02 or larger (the 0 volt input only
powers the electronics not the load).
M6 Input stud = Power Input and should be protected by a suitable protection
device at source.
M6 Output stud = Stabilized Power Output.
M4 -Ve stud = 0 volt connection for electronics.
12 volt 100A, 24 volt 50 & 100 Amp Versions
The wiring for the input & output connections must be completed
using suitably rated cable and overload protection for the input wiring
must be installed at source.
M8 Input + stud = Power Input.
M8 Power Output + stud = Stabilized Power Output.
M4 0v / earth stud = 0 volt connection for electronics.
M4 O/P V Sense stud = option facility for remote voltage sensing. If
remote sensing is not required link to the M8 Power Output stud in NO circumstances
must it be left disconnected.
Mechanical Installation
| For 12 volt Amp versions flange mounting via 2 x M4 fixing screws on each flange. | |
| For 12 volt 15 Amp & 25 Amp versions flange mounting via 2 x M5 fixing bolts on each flange. | |
| For 12 volt 50 Amp & 24 volt 25 Amp versions flange mounting via 2 x M5 fixing bolts on each flange. | |
| For 12 volt 100A & 24 volt 50 & 110AHr versions flange mounting via 3 x M5 fixing bolts on each flange. | |
| Mount in area not subject to water ingress or high levels of humidity. | |
| As the 12 volt Amp, 15 Amp & 25 Amp versions are convection cooled mount the units in an area where the free flow of air is not restricted and the ambient temperature is below the prescribed limits. | |
| As the 12 volt 50 Amp, 12 volt 110AHr, 24 volt 25 Amp, 50 Amp & 110AHr units are fan cooled allow a minimum of 250 mm to the top of the unit and 300 mm at the front for cooling purposes. | |
| Do not mount near to other equipment which generates high temperature levels |